Genset Model | 30GFT |
Structure | integrated |
Exciting Method | AVR Brushless |
Rated Power ( kW/kVA ) | 30/37.5 |
Rated Current ( A ) | 54 |
Rated Voltage ( V ) | 230/400 |
Rated Frequency ( Hz ) | 50/60 |
Rated Power Factor | 0.8 LAG |
No Load Voltage Range | 95% ~ 105% |
Stable Voltage Regulation Rate | ≤±1% |
Instantaneous Voltage Regulation Rate | ≤-15% ~ +20% |
Voltage Recover Time | ≤3 S |
Voltage Fluctuation Rate | ≤±0.5% |
Instantaneous Frequency Regulation Rate | ≤±10% |
Frequency Stabilization Time | ≤5 S |
Line-voltage Waveform Sinusoidal Distortion Rate | ≤2.5% |
Overall Dimension ( L*W*H ) ( mm ) | 1900*900*1400 |
Net Weight ( kg ) | 920 |
Noise dB ( A ) | <93 |
Overhaul Cycle ( h ) | 20000 |
Model | NW52D4 ( Ricardo Technology ) |
Type | Inline, 4 strokes, electric control ignition, pre-mixed stoichiometry burn, natural aspiration |
Cylinder Number | 4 |
Bore*Stroke ( mm ) | 110*135 |
Total Displacement ( L ) | 5.132 |
Rated Power ( kW ) | 40 |
Rated Speed ( r/min ) | 1500/1800 |
Fuel Type | Biomass gas |
Oil (L) | 7 |
Model | 30KZY, NPT brand |
Display Type | Multi-function LCD display |
Control Module | HGM9320 or HGM9510, Smartgen brand |
Operation Language | English |
Model | XN184H |
Brand | XN ( Xingnuo ) |
Shaft | Single bearing |
Rated Power ( kW/kVA ) | 30/37.5 |
Enclosure Protection | IP23 |
Efficiency ( % ) | 86.6 |
Cogeneration is most effective when the heat can be used on-site or very close; but when the heat must be transported over a long distance, the overall efficiency is reduced: this requires highly insulated pipes, which are expensive and inefficient; and Electricity can be transmitted along relatively simple wires, and can be transmitted over longer distances for the same energy loss.