(1) The water seal of the low-pressure covered biogas tank should maintain the height of the water seal, and anti-freezing measures should be taken in cold areas;
(2) The biogas should be fully utilized, and the biogas to be discharged should be flared;
(3) Check and record the gas storage volume and pressure of the biogas tank on time;
(4) The steam pipeline connected with the biogas tank and the condensed water in the biogas pipeline should be discharged regularly;
(5) The desulfurizer in the desulfurization device should be regenerated or replaced regularly;
(6) The pH value of the water in the water seal tank of the biogas tank should be measured regularly. When the pH value is less than 6, the water should be changed;
(7) The pressure of the biogas tank should be 2500-4000Pa.